How to get it right: Notches & holes in solid timber joists

Blog Post
Notches and holes in solid timber joists

When installing pipework or cabling, floor or ceiling joists may need to be notched or drilled. But this could weaken the floor to such an extent that it becomes structurally unsound.

To find out if this might be the case, you can find guidance on notches and holes in solid timber joists for use in domestic properties in section 3.2.2 of Eurocode 5 published by BM TRADA.

The diagrams and tables below illustrate the zones and sizes permissible for differing spans and joist depths.

Notches and holes in sold timber joists - diagram 1Notches and holes in solid timber joists

 

Span of timber Hole locations between Notching locations between
mm 0.25 of span 0.4 of span 0.07 of span 0.25 of span
2000 500 800 140 500
2500 625 1000 175 625
3000 750 1200 210 750
3500 875 1400 245 875
4000 1000 1600 280 1000
4500 1125 1800 315 1125

 

Depth of timber Max hole diameter Max notch depth
mm 0.25 x depth mm 0.125 x depth mm
100 25.0 12.5
125 31.3 15.6
150 37.5 18.8
175 43.8 21.9
200 50.0 25.0
225 56.3 28.1
250 62.5 31.3
275 65 (max) 34.4
300 65 (max) 35 (max)

Key points for notches and holes

Before you start work check that the joist size is adequate for the span.

Notches can only be made in the top OR bottom of the joists, (not both) within the permitted area to a maximum of 35mm.

Holes may only be made on the joist's centreline within the permitted area to a maximum diameter of 65mm.

Additional holes must be at least three diameters (centre to centre) apart.

Single/multiple timber structural beams, rafters, purlins and binders must never be notched or drilled without calculations to justify the remaining timber. Rafters may be birdsmouthed by no more than 1/3rd of the depth.

This guidance does not apply to engineered joists e.g. JJI joists and reference should be made to specific product manufacturers instructions.

Further reading

How to get it right: Supporting joists on external walls

 


Please Note: Every care was taken to ensure the information was correct at the time of publication. Any written guidance provided does not replace the user’s professional judgement. It is the responsibility of the dutyholder or person carrying out the work to ensure compliance with relevant building regulations or applicable technical standards.

This article was reviewed and updated on 10 August 2023

Comments

LABC Response

Submitted 11 months 2 weeks ago

LABC is unable to provide specific advice to you. However the joists will need sufficient bearing into the wall and therefore the advice provided in the article shows the areas in which holes can be considered.

Best,
LABC Team

Drilling multiple joists

Submitted 10 months ago

Does this advice imply that it's ok to drill multiple adjacent joists (eg. 3 to get a shower waste into soil stack) as long as the rules are followed?

Thanks

LABC Response

Submitted 7 months ago

Thank you for your enquiry, however, this is not something that LABC can help with.

Please discuss the details of your proposals with your professional advisors such as your contractor and if necessary, a structural engineer.

Best,
LABC Team

Incorrect information?

Submitted 10 months ago

"Notches can only be made in the top OR bottom of the joists"

My understanding notches on the underside of the joist was not allowed? Is this an error?

LABC Response

Submitted 6 months 3 weeks ago

Thank you for your enquiry.

As described in the article, notches can only be made in the top or bottom of the joists, but not both. Eurocode 5, span tables for solid timber members in floors, ceilings, and roofs for dwellings, published by BM TRADA, section 3.2.2, gives further guidance on this.

Best,
LABC Team

Ychwanegu sylw newydd

This question is for testing whether or not you are a human visitor and to prevent automated spam submissions.

Sign up to the building bulletin newsletter

Over 48,000 construction professionals have already signed up for the LABC Building Bulletin.



Join them and receive useful tips, practical technical information and industry news by email once every 6 weeks.



Subscribe to the Building Bulletin